Modern Office Strandards Poland 2020
Recommendation: • Achieve maximum % net to gross ratio for particular type of the building • Allow at least 13 cubic metres volume of free space per person and 2 sq m area of free floor space per person (*2) • For offices lower than 3m from floor to ceiling allow at least 15 cubic metres volume of free space per person
City One / Wroclaw
/ CBRE / Rolfe Judd / Modern Office Standards Poland 2020 B2 / Internal layout and grids C) OCCUPANCY LEVELS
Typical office occupancy levels range from 6–7 sq m per person. It is recommended that all of- fice buildings are designed to allow for 1 person per 7 sq m in the design of all building services. A word of warning however; if it is intended that the building should cater for a more dense occu-
pation of a call centre, trading facilities or other high density uses then densities of 1 person per 5 sq m may be reached and should be catered for. New ways of working, including coworking spaces fall into the limits.
D) CIRCULATION
To meet statutory requirements — it is common practice however to provide office circulation corri- dors wider than that required for fire escape provision.
Recommendation:
Means of escape: • 5 sq m per person (for calculation if office internal layout is not provided) (*1) • Escape route minimum clear width 1.4m / 0.6m per every 100 people (counted proportionally) (*1) • Escape door minimum clear width 0.9m / 0.6m per every 100 people (counted proportionally) (*1) • Stairs flight minimum clear width 1.2m / 0.6 m per every 100 people (counted proportionally) (*1) • Means of escape is usually the driving factor to achieve optimum size / layout of the floor space
19
/