Modern Office Strandards Poland 2020
Modern Office Standards Poland 2020 / Rolfe Judd / CBRE /
Recommendation: Heating Cooling & Ventilation (*8)
B) INTERNAL HEAT GAINS — SMALL POWER
• Office equipment (diversified load): 30 W/ sq m based on 7 sq m/ person occupancy ratio and 80% utilization factor • Risers / bus bars on floor distribution boards: 2% of installed power • Heat gains from low voltage systems (security, fire detection, etc.) are so small that they are usually omitted
Internal design temperatures according to PN-EN 15251:2012 and PN-EN 7730:2006:
Winter 20,0–24,0°C (*8), recommended 21,0°C
•
Summer 23,0–26,0°C (*8), recommended 24,0°C
•
With air velocity not higher than the mandatory one
/ CBRE / Rolfe Judd / Modern Office Standards Poland 2020
Heating, cooling and ventilation / B19
C) INTERNAL HEAT GAINS — IT SERVICES
Winter max 0,15 m/s
• •
Summer max 0,18 m/s
Central server room: 30 kW
• •
Local distribution points: 10 kW
Mechanical Ventilation Rates •
Minimum fresh air is legally required at 30 cubic m per hour per person, however it is recom- mended to provide 40–50 cubic m per hour per person (*7). Higher exchange creates better internal environment. It should be noted that best practice is typically set over a minimum level of 36m 3 per hour per person recommended during BREEAM certification. Recommended value of CO2 concentration [ppm] above the concentration in the outside air for A class buildings is at the level of 350ppm (maximum 500ppm) (*8) • Assume higher Ventilation Rates than provided in the regulations • Fresh air supply provided also in the spaces dedicated for coffee points and kitchens • Higher air supply for the conference rooms (individual control panels)
D) INTERNAL HEAT GAINS — LIGHTING
5–10 W/ sq m
•
B19 / Heating, cooling and ventilation
E) INTERNAL HEAT GAINS — OCCUPANTS
150 W/ person
•
Humidity Control •
40–60% in summer and winter
Free cooling system
•
• Dedicated HVAC for medic and fitness sector — and some spar air to distribute
Thermal environment meets the requirements of category A in the building, if the temperature is met in at least 95% of the rooms used class A requirements by more than 97% time of use during the year; speed air and noise in at least 95% rooms used do not exceed the limit values.